Residual current circuit breaker with overcurrent protection Hager ADM466C (4P, 16A, C, type A, 30mA, 6kA)

SKU:HADM466C
On Stock
  • Type: Residual current circuit breaker with overcurrent protection (RCBO)
  • Model: Hager ADM466C
  • Number of poles: 4P
  • Rated current: 16 A
  • Tripping characteristic: C
  • Residual current: 30 mA
  • Short-circuit capacity: 6 kA
  • Type: A (suitable for AC and pulsating DC currents)
  • Brand: Hager
€151.65
Tax included Delivery within 1–3 business days
Quantity

  • General
  • Rated current16 A
  • Rated residual operating current Idn30 mA
  • Rated short-circuit breaking capacity Icn (400 V AC, IEC 60898-1)6 kA
  • Rated current at –25 °C19.40 A
  • Rated current at –20 °C19.10 A
  • Rated current at –15 °C18.90 A
  • Rated current at –10 °C18.60 A
  • Rated current at –5 °C18.30 A
  • Rated current at 0 °C18.00 A
  • Rated current at 5 °C17.60 A
  • Rated current at 10 °C17.30 A
  • Rated current at 15 °C17.00 A
  • Rated current at 20 °C16.70 A
  • Rated current at 25 °C16.30 A
  • Rated current at 30 °C16.00 A
  • Rated current at 35 °C15.60 A
  • Rated current at 40 °C15.20 A
  • Rated current at 45 °C14.90 A
  • Rated current at 50 °C14.40 A
  • Rated current at 55 °C14.00 A
  • Rated current at 60 °C13.60 A
  • Curve typeC
  • Neutral positionLeft, Right
  • Pole type4P
  • Number of protected poles4
  • Number of modules4
  • Residual current typeA
  • Ingress Protection (IP) classIP2X
  • Voltage supply typeAC
  • Rated operational voltage Ue230–400 V
  • Rated insulation voltage Ui500 V
  • Dielectric strength (power frequency)2 kV
  • Rated impulse withstand voltage Uimp4,000 V
  • Overvoltage category (IEC 60947-1)3
  • Nominal tightening torque (top terminal)2 Nm
  • Nominal tightening torque (bottom terminal)2 Nm
  • Nominal tightening torque (general)2 Nm
  • 360° mounting positionYes
  • Top connection type (modular devices)Screw terminal
  • Bottom connection type (modular devices)Biconnect
  • Rated short-circuit breaking capacity Icn AC (IEC 60898-1)6 kA
  • Frequency50 Hz
  • Input cross-section (flexible conductors)1–16 mm²
  • Input cross-section (rigid conductors)1–25 mm²
  • Energy limitation class I²t3
  • Operating temperature–25 to +40 °C
  • Height84 mm
  • Width71 mm
  • Depth70 mm
  • Connection typeScrew terminal
  • Total power loss at In10.90 W
HADM466C